The following definitions of comment descriptions represent this inspection
report. All comments by the inspector should be considered before purchasing
this home. Any recommendations by the inspector to repair or replace suggests a
second opinion or further inspection by a qualified contractor. All costs
associated with further inspection fees and repair or replacement of item,
component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item,
component or unit and if no other comments were made then it appeared to be
functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item,
component or unit and made no representations of whether or not it was
functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is
not in this home or building.
Repair or Replace (RR) = The item, component or unit
is not functioning as intended, or needs further inspection by a qualified
contractor. Items, components or units that can be repaired to satisfactory
condition may not need replacement.
The home inspector shall observe: Roof covering; Roof
drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and
Signs of' leaks or abnormal condensation on building components. The home
inspector shall: Describe the type of roof covering materials; and Report
the methods used to observe the roofing. The home inspector is not required
to: Walk on the roofing; or Observe attached accessories including but not
limited to solar systems, antennae, and lightning arrestors.
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
IN
NI
NP
RR
Inspection Items
X
1.0
ROOF COVERINGS
Roof Covering:
3-Tab fiberglass
Viewed roof covering from:
Ground
Comments:
(1) The roof covering is old, and the life of covering has expired. The
covering does need to be replaced. While it could last a year or so, some
areas may need patching with tar as leaks develop. Some shingles are missing
on main roof and daylight can be seen from attic. Immediate repairs are
needed here.
1.0 Picture 1
1.0 Picture 2
(2) The tree limbs that are in contact with roof or hanging near roof should
be trimmed.
1.0 Picture 3
X
1.1
FLASHINGS Comments:
X
1.2
SKYLIGHTS,
CHIMNEYS AND ROOF PENETRATIONS
Sky Light(s):
None
Chimney (exterior):
Brick
Comments:
X
1.3
ROOF DRAINAGE
SYSTEMS Comments:
(1) The gutter is loose or daylight between gutters and fascia at the rear.
Loose or leaking gutters can cause deterioration of fascia, soffit or roof
edge. It can also cause gutters to pull loose and lead to possible water
intrusion. A qualified contractor should inspect and repair as needed.
1.3 Picture 1
(2) The gutter screens collapsed inside gutter at the front of home. A
qualified person should repair or replace as needed. The gutter needs
cleaning of debris at the front and as needed elsewhere. Gutters that drain
poorly or clogged can lead to many costly problems such as deterioration of
fascia, soffit or roof edge. It can also cause gutters to pull loose and
lead to possible water intrusion. A qualified person should repair or
replace as needed.
1.3 Picture 2
IN
NI
NP
RR
Inspection Items
IN=Inspected, NI=Not Inspected, NP=Not
Present, RR=Repair or Replace
The home inspector shall observe: Wall cladding,
flashings, and trim; Entryway doors and a representative number of windows;
Garage door operators; Decks, balconies, stoops, steps, areaways, porches
and applicable railings; Eaves, soffits, and fascias; and Vegetation,
grading, drainage, driveways, patios, walkways, and retaining walls with
respect to their effect on the condition of the building. The home inspector
shall: Describe wall cladding materials; Operate all entryway doors and a
representative number of windows; Operate garage doors manually or by using
permanently installed controls for any garage door operator; Report whether
or not any garage door operator will automatically reverse or stop when
meeting reasonable resistance during closing; and Probe exterior wood
components where deterioration is suspected. The home inspector is not
required to observe: Storm windows, storm doors, screening, shutters,
awnings, and similar seasonal accessories; Fences; Presence of safety
glazing in doors and windows; Garage door operator remote control
transmitters; Geological conditions; Soil conditions; Recreational
facilities (including spas, saunas, steam baths, swimming pools, tennis
courts, playground equipment, and other exercise, entertainment, or athletic
facilities); Detached buildings or structures; or Presence or condition of
buried fuel storage tanks. The home inspector is not required to: Move
personal items, panels, furniture, equipment, plant life, soil, snow, ice or
debris that obstructs access or visibility.
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
IN
NI
NP
RR
Inspection Items
X
2.0
WALL CLADDING
FLASHING AND TRIM
Siding Style:
Brick
Siding Material:
Wood, Full brick
Comments:
X
2.1
DOORS (Exterior)
Exterior Entry Doors:
Wood
Comments:
The side entry door to basement reveals daylight when latched at areas
missing weather-stripping. This is a small repair. A qualified person should
repair or replace as needed.
2.1 Picture 1 Basement entry
X
2.2
WINDOWS Comments:
The sill plate is deteriorated at right side (facing front). This is a small
repair. A qualified person should repair or replace as needed.
(1) The support column(s) on covered porch at the left side (facing front)
are split or cracked in areas and are deteriorated in areas. A repair or
replacement is needed. A qualified contractor should perform the work.
2.3 Picture 1 Front Porch
(2) The steps on the porch at the rear of home are not uniform in"riser
height" and are a tripping hazard. A fall or injury could occur if not
corrected. I recommend repair as needed.
2.3 Picture 2 Rear Porch
(3) Some of the rafters of covered porch shows weakening by previous damage
from leaks or other. Appears to remain strong to function. FYI
2.3 Picture 3
X
2.4
VEGETATION,
GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With
respect to their effect on the condition of the building)
Driveway:
Asphalt
Comments:
X
2.5
EAVES, SOFFITS AND
FASCIAS Comments:
(1) The eave boards at eave on the gables and various roof edges are
deteriorated. Repairs are needed. A qualified contractor should inspect and
repair as needed.
2.5 Picture 1
2.5 Picture 2
(2) The soffit panel at eave on the front (right of main entry) are
weathered and peeling paint. Further deterioration may occur if not
repaired. A qualified person should repair or as needed. I am unable to
determine if leak exists here or was a result of clogged gutters.
2.5 Picture 3 Front (right of main entry)
IN
NI
NP
RR
Inspection Items
IN=Inspected, NI=Not Inspected, NP=Not
Present, RR=Repair or Replace
The home inspector shall observe: Walls, ceiling, and
floors; Steps, stairways, balconies, and railings; Counters and a
representative number of installed cabinets; and A representative number of
doors and windows. The home inspector shall: Operate a representative number
of windows and interior doors; and Report signs of abnormal or harmful water
penetration into the building or signs of abnormal or harmful condensation
on building components. The home inspector is not required to observe:
Paint, wallpaper, and other finish treatments on the interior walls,
ceilings, and floors; Carpeting; or Draperies, blinds, or other window
treatments.
Living Room
Dining Room
Kitchen
IN=Inspected, NI=Not Inspected, NP=Not
Present, RR=Repair or Replace
(1) Plaster ceiling is in need of repair in bathroom. Currently it is
covered by drop panels.
3.0 Picture 1
(2) The Ceiling Tile on the ceiling reveals a water stain indicating a leak
did or still exists at the Bedroom. Due to recent dry weather, I am unable
to determine if the leak still exists. A qualified contractor should inspect
and repair as needed.
3.0 Picture 2
X
3.1
WALLS
Wall Material:
Drywall, Plaster
Comments:
X
3.2
FLOORS
Floor Covering(s):
Hardwood T&G, Tile, Vinyl
Comments:
X
3.3
STEPS, STAIRWAYS,
BALCONIES AND RAILINGS Comments:
The hand/guard rail for the stairs to basement are missing balusters (on
both sides). A fall or injury could occur if not corrected. A qualified
contractor should repair or replace as needed.
3.3 Picture 1 basement stairs
3.3 Picture 2
X
3.4
COUNTERS AND A
REPRESENTATIVE NUMBER OF CABINETS
Cabinetry:
Wood, Veneer
Countertop:
Laminate
Comments:
Sink base is damaged under sink at bottom shelf likely from leaking faucet.
Recommend repair or replace sink base cabinetry as necessary.
3.4 Picture 1 under kitchen sink
X
3.5
DOORS
(REPRESENTATIVE NUMBER)
Interior Doors:
Wood
Comments:
The Entry door and Closet door rubs at jamb when closing at the Living Room
and hallway closet and Small bedroom. The Living room second door to porch
is painted shut or will not open. A qualified person should repair or
replace as needed.
X
3.6
WINDOWS
(REPRESENTATIVE NUMBER)
Window Types:
Double-hung, Single pane, Storm windows
Comments:
There are cracked and broken glass at numerous windows throughout home. At
least five windows missing sash cords at the Living Room, pantry and Small
bedroom (left of hall bath) and at top of stairs. A qualified person should
repair or replace as needed.
IN
NI
NP
RR
Inspection Items
IN=Inspected, NI=Not Inspected, NP=Not
Present, RR=Repair or Replace
The Home Inspector shall observe structural components
including foundations, floors, walls, columns or piers, ceilings and roof.
The home inspector shall describe the type of Foundation, floor structure,
wall structure, columns or piers, ceiling structure, roof structure. The
home inspector shall: Probe structural components where deterioration is
suspected; Enter under floor crawl spaces, basements, and attic spaces
except when access is obstructed, when entry could damage the property, or
when dangerous or adverse situations are suspected; Report the methods used
to observe under floor crawl spaces and attics; and Report signs of abnormal
or harmful water penetration into the building or signs of abnormal or
harmful condensation on building components. The home inspector is not
required to: Enter any area or perform any procedure that may damage the
property or its components or be dangerous to or adversely effect the health
of the home inspector or other persons.
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
IN
NI
NP
RR
Inspection Items
X
4.0
FOUNDATIONS,
BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration
into the building or signs of abnormal or harmful condensation on building
components.)
Foundation:
Brick
Method used to observe
Crawlspace: No crawlspace
Comments:
(1) Brick Foundation wall at the basement entry has missing mortar around
windows . Repairs are needed. A skilled masonry contractor should perform
the repairs.
4.0 Picture 1
(2) The brick foundation has been coated with a water proof sealer except
behind shelving. If water intrusion occurs here, then shelving may need
removing in order to coat area properly.
4.0 Picture 2 basement wall
X
4.1
WALLS (Structural)
Wall Structure:
Wood, Brick
Comments:
X
4.2
COLUMNS OR PIERS
Columns or Piers:
Masonry block, Supporting walls
Comments:
X
4.3
FLOORS
(Structural)
Floor Structure:
2 X 8, 2 X 10, Wood joists
Comments:
X
4.4
CEILINGS
(structural)
Ceiling Structure:
2X4
Comments:
X
4.5
ROOF STRUCTURE AND
ATTIC
Roof Structure:
Stick-built, 2 X 6 Rafters, Common board
Roof-Type:
Gable
Method used to observe
attic: Walked
Attic info:
Attic access
Comments:
The common board roofing indicates roof leaks or has leaked around the
chimneys. Leaking roofs should be repaired to prevent damage. I recommend a
qualified contractor perform the work. (See Roof Coverings comments)
4.5 Picture 1
IN
NI
NP
RR
Inspection Items
IN=Inspected, NI=Not Inspected, NP=Not
Present, RR=Repair or Replace
The home inspector shall observe: Interior water supply
and distribution system, including: piping materials, supports, and
insulation; fixtures and faucets; functional flow; leaks; and cross
connections; Interior drain, waste, and vent system, including: traps;
drain, waste, and vent piping; piping supports and pipe insulation; leaks;
and functional drainage; Hot water systems including: water heating
equipment; normal operating controls; automatic safety controls; and
chimneys, flues, and vents; Fuel storage and distribution systems including:
interior fuel storage equipment, supply piping, venting, and supports;
leaks; and Sump pumps. The home inspector shall describe: Water supply and
distribution piping materials; Drain, waste, and vent piping materials;
Water heating equipment; and Location of main water supply shutoff device.
The home inspector shall operate all plumbing fixtures, including their
faucets and all exterior faucets attached to the house, except where the
flow end of the faucet is connected to an appliance. The home inspector is
not required to: State the effectiveness of anti-siphon devices; Determine
whether water supply and waste disposal systems are public or private;
Operate automatic safety controls; Operate any valve except water closet
flush valves, fixture faucets, and hose faucets; Observe: Water conditioning
systems; Fire and lawn sprinkler systems; On-site water supply quantity and
quality; On-site waste disposal systems; Foundation irrigation systems;
Spas, except as to functional flow and functional drainage; Swimming pools;
Solar water heating equipment; or Observe the system for proper sizing,
design, or use of proper materials.
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
IN
NI
NP
RR
Inspection Items
X
5.0
PLUMBING DRAIN,
WASTE AND VENT SYSTEMS
Washer Drain Size:
2" Diameter
Plumbing Waste:
PVC, Cast iron, lead waste (old)
Comments:
(1) Upon arriving water was on and spilling onto floor of basement from
nearby faucet and water heater. The hvac person who was their at the time of
inspection claimed that he turned the water on at the street. I turned off
the valve at faucet and water heater. FYI
5.0 Picture 1
(2) The stop-valve does not work properly at the Hall Bath sink. Repairs are
needed. The tub drain drains slowly at main bath. There is a leak under
bathtub that can be seen from removing access panel on wall. Repairs are
needed. A qualified licensed plumber should repair or correct as needed.
5.0 Picture 2 Upstairs bath
(3) The basket strainer is leaking at left side and at right side at the
Kitchen sink. Repairs are needed. A qualified licensed plumber should repair
or correct as needed.
5.0 Picture 3
(4) The floor drain has a plug as if to keep something from coming in? After
the inspection, the owner of the adjacent property volunteered information
that the city sewer occasionally will back up and come into basement. This
may be the reason for the plug? I am unable to determine if plug will
prevent this from occurring. FYI
5.0 Picture 4 basement floor drain
X
5.1
PLUMBING WATER
SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
Water Source:
Public
Water Filters:
None
Plumbing Water Supply (into
home): Galvanized (old)
Plumbing Water Distribution
(inside home): Galvanized, Copper
Comments:
(1) The lever on faucet leaks at the kitchen sink. Repairs are needed to
stop leaking water from further damaging the cabinet bottom or to eliminate
moisture that may contribute to fungi growth. I recommend repair as
necessary by a qualified person. The spray nozzle is not working properly
which could be as a result of no volume or pressure at the kitchen sink.
Repairs are needed. A qualified licensed plumber should repair or correct as
needed.
(2) The water pressure over-all is poor and would not pass "functional
flow." A possible reason for weak volume or pressure could be old galvanized
piping that is corroded inside. NOTE: NO SHOWER FOR BATH
Toilet will not fill with water likely due to clogged piping. I could not
inspect the toilet fixture for leaks.
5.1 Picture 1
5.1 Picture 2
X
5.2
HOT WATER SYSTEMS,
CONTROLS, CHIMNEYS, FLUES AND VENTS
Water Heater Power Source:
Electric
Water Heater Capacity:
40 Gallon (1-2 people)
Manufacturer:
A.O. SMITH
Comments:
Water heater was empty and drain open at bottom when I arrived. I closed
drain but at the end of inspection, drips were still occurring. Repairs may
be needed.
5.2 Picture 1
5.2 Picture 2
X
5.3
MAIN WATER
SHUT-OFF DEVICE (Describe location) Comments:
The main shut off is the red knob located in the basement on the front wall.
This is for your information.
5.3 Picture 1
X
5.4
FUEL STORAGE AND
DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) Comments:
X
5.5
MAIN FUEL SHUT OFF
(Describe Location) Comments:
The main
fuel shut off is at gas meter outside
X
5.6
SUMP PUMP Comments:
IN
NI
NP
RR
Inspection Items
IN=Inspected, NI=Not Inspected, NP=Not
Present, RR=Repair or Replace
The home inspector shall observe: Service entrance
conductors; Service equipment, grounding equipment, main over current
device, and main and distribution panels; Amperage and voltage ratings of
the service; Branch circuit conductors, their over current devices, and the
compatibility of their ampacities and voltages; The operation of a
representative number of installed ceiling fans, lighting fixtures, switches
and receptacles located inside the house, garage, and on the dwelling's
exterior walls; The polarity and grounding of all receptacles within six
feet of interior plumbing fixtures, and all receptacles in the garage or
carport, and on the exterior of inspected structures; The operation of
ground fault circuit interrupters; and Smoke detectors. The home inspector
shall describe: Service amperage and voltage; Service entry conductor
materials; Service type as being overhead or underground; and Location of
main and distribution panels. The home inspector shall report any observed
aluminum branch circuit wiring. The home inspector shall report on presence
or absence of smoke detectors, and operate their test function, if
accessible, except when detectors are part of a central system. The home
inspector is not required to: Insert any tool, probe, or testing device
inside the panels; Test or operate any over current device except ground
fault circuit interrupters; Dismantle any electrical device or control other
than to remove the covers of the main and auxiliary distribution panels; or
Observe: Low voltage systems; Security system devices, heat detectors, or
carbon monoxide detectors; Telephone, security, cable TV, intercoms, or
other ancillary wiring that is not a part of the primary electrical
distribution system; or Built-in vacuum equipment.
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
IN
NI
NP
RR
Inspection Items
X
6.0
SERVICE ENTRANCE
CONDUCTORS
Electrical Service Conductors:
Overhead service, Aluminum, 220 volts
Comments:
X
6.1
SERVICE AND
GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS
Panel capacity:
100 AMP
Panel Type:
Fuses, Circuit breakers
Comments:
X
6.2
BRANCH CIRCUIT
CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE
Branch wire 15 and 20 AMP:
Copper
Wiring Methods:
Romex, Knob and Tube
Comments:
Problem(s) discovered with Branch Circuits such as doubled wiring at
fuse(s), doubled wiring at circuit(s), and edison base fuse(s) under stairs,
and any other problems that an electrician may discover while performing
repairs need correcting. I recommend a licensed electrician inspect further
and correct as needed.
6.2 Picture 1
6.2 Picture 2
X
6.3
CONNECTED DEVICES
AND FIXTURES (Observed from a representative number operation of ceiling fans,
lighting fixtures, switches and receptacles located inside the house, garage,
and on the dwelling's exterior walls) Comments:
(1) "Two-prong" outlets are missing cover-plates in the dining room and in
the living room. This is a safety issue that needs to be corrected. I
recommend repair as needed.
6.3 Picture 1 various rooms
(2) Loose light fixture needs securing in closet. Loose or unfinished wiring
in attic should be corrected to remain safe ( Picture 2 ) .One splice box
needs a cover-plate in the basement. I recommend repair as needed ( Picture
4 ) .
6.3 Picture 2
6.3 Picture 3
6.3 Picture 4
X
6.4
POLARITY AND
GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL
RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE Comments:
X
6.5
OPERATION OF GFCI
(GROUND FAULT CIRCUIT INTERRUPTERS) Comments:
X
6.6
LOCATION OF MAIN
AND DISTRIBUTION PANELS Comments:
The main
panel box is located at the basement.
X
6.7
SMOKE DETECTORS Comments:
X
6.8
CARBON MONOXIDE
DETECTORS Comments:
IN
NI
NP
RR
Inspection Items
IN=Inspected, NI=Not Inspected, NP=Not
Present, RR=Repair or Replace
The home inspector shall observe permanently installed
heating and cooling systems including: Heating equipment; Cooling Equipment
that is central to home; Normal operating controls; Automatic safety
controls; Chimneys, flues, and vents, where readily visible; Solid fuel
heating devices; Heat distribution systems including fans, pumps, ducts and
piping, with supports, insulation, air filters, registers, radiators, fan
coil units, convectors; and the presence of an installed heat source in each
room. The home inspector shall describe: Energy source; and Heating
equipment and distribution type. The home inspector shall operate the
systems using normal operating controls. The home inspector shall open
readily openable access panels provided by the manufacturer or installer for
routine homeowner maintenance. The home inspector is not required to:
Operate heating systems when weather conditions or other circumstances may
cause equipment damage; Operate automatic safety controls; Ignite or
extinguish solid fuel fires; or Observe: The interior of flues; Fireplace
insert flue connections; Humidifiers; Electronic air filters; or The
uniformity or adequacy of heat supply to the various rooms.
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
IN
NI
NP
RR
Inspection Items
X
7.0
HEATING EQUIPMENT
Heat Type:
Circulating boiler
Energy Source:
Gas
Number of Heat Systems
(excluding wood): One
Comments:
The gas-fired boiler did not function or is non-operational. A repair or
replacement is needed. I recommend further inspection by a licensed HVAC
contractor.
7.0 Picture 1
7.0 Picture 2
X
7.1
NORMAL OPERATING
CONTROLS Comments:
X
7.2
AUTOMATIC SAFETY
CONTROLS Comments:
X
7.3
DISTRIBUTION
SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air
filters, registers, radiators, fan coil units and convectors) Comments:
Due to the concern for water volume or pressure and because of the old
piping that was turned off for an extended period of time, and the fact that
the boiler is non-operational, I am concerned of whether or not the
radiators will function properly when boiler is repaired. A clogged or
failed radiator can be expensive to replace. I strongly recommend that an
HVAC person inspect all the radiators when boiler becomes operable. You
should obtain a letter from the HVAC company as to the condition of
radiators, piping and boiler before you close on home.
X
7.4
PRESENCE OF
INSTALLED HEAT SOURCE IN EACH ROOM Comments:
There is no heat source for Bedroom on right (at top of stairs).
7.4 Picture 1 bedroom
X
7.5
CHIMNEYS, FLUES
AND VENTS (for fireplaces, gas water heaters or heat systems) Comments:
The liner for fireplace was partially visible and appears good except for
creosote dust that may conceal a hairline crack until cleaned and inspected
by a licensed chimney sweep. I did not inspect the liner for gas fired
boiler. For a detailed inspection of liner, I recommend a qualified chimney
sweep inspect for safety.
The home inspector shall observe: Insulation and vapor
retarders in unfinished spaces; Ventilation of attics and foundation areas;
Kitchen, bathroom, and laundry venting systems; and the operation of any
readily accessible attic ventilation fan, and, when temperature permits, the
operation of any readily accessible thermostatic control. The home inspector
shall describe: Insulation in unfinished spaces; and Absence of insulation
in unfinished space at conditioned surfaces. The home inspector shall: Move
insulation where readily visible evidence indicates the need to do so; and
Move insulation where chimneys penetrate roofs, where plumbing drain/waste
pipes penetrate floors, adjacent to earth filled stoops or porches, and at
exterior doors. The home inspector is not required to report on: Concealed
insulation and vapor retarders; or Venting equipment that is integral with
household appliances.
IN=Inspected, NI=Not
Inspected, NP=Not Present, RR=Repair or Replace
IN
NI
NP
RR
Inspection Items
X
8.0
INSULATION IN
ATTIC
Attic Insulation:
Blown, Fiberglass, R-19 or better
Comments:
The attic has a small amount of insulation and "Knob and Tube" wiring is
present. As a safety rule Knob and Tube wiring should never have insulation
covering this wire or over heating can occur. If new insulation is added, an
electrician should first replace knob and tubing wires with updated wiring.
X
8.1
INSULATION UNDER
FLOOR SYSTEM
Floor System Insulation:
NONE
Comments:
X
8.2
VAPOR RETARDERS
(ON GROUND IN CRAWLSPACE OR BASEMENT) Comments:
X
8.3
VENTILATION OF
ATTIC AND FOUNDATION AREAS
Ventilation:
Gable vents, Passive
Comments:
X
8.4
VENTING SYSTEMS
(Kitchens, baths and laundry)
Exhaust Fans:
None
Dryer Power Source:
220 Electric
Dryer Vent:
Flexible Vinyl
Comments:
X
8.5
VENTILATION FANS
AND THERMOSTATIC CONTROLS (ATTIC) Comments:
IN
NI
NP
RR
Inspection Items
IN=Inspected, NI=Not Inspected, NP=Not
Present, RR=Repair or Replace
The home inspector shall observe and operate the basic
functions of the following kitchen appliances: Permanently installed
dishwasher, through its normal cycle; Range, cook top, and permanently
installed oven; Trash compactor; Garbage disposal; Ventilation equipment or
range hood; and Permanently installed microwave oven. The home inspector is
not required to observe: Clocks, timers, self-cleaning oven function, or
thermostats for calibration or automatic operation; Non built-in appliances;
or Refrigeration units. The home inspector is not required to operate:
Appliances in use; or Any appliance that is shut down or otherwise
inoperable.
IN=Inspected, NI=Not Inspected,
NP=Not Present, RR=Repair or Replace
IN
NI
NP
RR
Inspection Items
X
9.0
DISHWASHER
Dishwasher Brand:
KENMORE
Comments:
X
9.1
RANGES/OVENS/COOKTOPS
Range/Oven:
NONE
Comments:
X
9.2
RANGE HOOD
Exhaust/Range hood:
NONE
Comments:
X
9.3
TRASH COMPACTOR Comments:
X
9.4
FOOD WASTE
DISPOSER
Disposer Brand:
IN SINK ERATOR
Comments:
X
9.5
MICROWAVE COOKING
EQUIPMENT
Built in Microwave:
NONE
Comments:
IN
NI
NP
RR
Inspection Items
IN=Inspected, NI=Not Inspected, NP=Not
Present, RR=Repair or Replace
The following items or discoveries indicate that
these systems or components do not function as intended or
adversely affects the habitability of the dwelling; or
warrants further investigation by a specialist, or requires
subsequent observation. This summary shall not contain
recommendations for routine upkeep of a system or component to keep it in
proper functioning condition or recommendations to upgrade or enhance the
function or efficiency of the home. This Summary is not the entire report.
The complete report may include additional information of concern to the
customer. It is recommended that the customer read the complete report.
1.
Roofing
1.0
ROOF COVERINGS
Repair
or Replace
(1) The roof covering is old, and the life of covering has
expired. The covering does need to be replaced. While it could
last a year or so, some areas may need patching with tar as
leaks develop. Some shingles are missing on main roof and
daylight can be seen from attic. Immediate repairs are needed
here.
(2) The tree limbs that are in contact with roof or hanging near
roof should be trimmed.
1.3
ROOF DRAINAGE SYSTEMS
Repair
or Replace
(1) The gutter is loose or daylight between gutters and fascia
at the rear. Loose or leaking gutters can cause deterioration of
fascia, soffit or roof edge. It can also cause gutters to pull
loose and lead to possible water intrusion. A qualified
contractor should inspect and repair as needed.
(2) The gutter screens collapsed inside gutter at the front of
home. A qualified person should repair or replace as needed. The
gutter needs cleaning of debris at the front and as needed
elsewhere. Gutters that drain poorly or clogged can lead to many
costly problems such as deterioration of fascia, soffit or roof
edge. It can also cause gutters to pull loose and lead to
possible water intrusion. A qualified person should repair or
replace as needed.
2.
Exterior
2.1
DOORS (Exterior)
Repair
or Replace
The side entry door to basement reveals daylight when latched at areas missing
weather-stripping. This is a small repair. A qualified person should repair or
replace as needed.
2.2
WINDOWS
Repair
or Replace
The sill plate is deteriorated at right side (facing front). This is a small
repair. A qualified person should repair or replace as needed.
(1) The support column(s) on covered porch at the left side
(facing front) are split or cracked in areas and are
deteriorated in areas. A repair or replacement is needed. A
qualified contractor should perform the work.
(2) The steps on the porch at the rear of home are not uniform
in"riser height" and are a tripping hazard. A fall or injury
could occur if not corrected. I recommend repair as needed.
(3) Some of the rafters of covered porch shows weakening by
previous damage from leaks or other. Appears to remain strong to
function. FYI
2.5
EAVES, SOFFITS AND FASCIAS
Repair
or Replace
(1) The eave boards at eave on the gables and various roof edges
are deteriorated. Repairs are needed. A qualified contractor
should inspect and repair as needed.
(2) The soffit panel at eave on the front (right of main entry)
are weathered and peeling paint. Further deterioration may occur
if not repaired. A qualified person should repair or as needed.
I am unable to determine if leak exists here or was a result of
clogged gutters.
3.
Interiors
3.0
CEILINGS
Repair
or Replace
(1) Plaster ceiling is in need of repair in bathroom. Currently
it is covered by drop panels.
(2) The Ceiling Tile on the ceiling reveals a water stain
indicating a leak did or still exists at the Bedroom. Due to
recent dry weather, I am unable to determine if the leak still
exists. A qualified contractor should inspect and repair as
needed.
3.3
STEPS, STAIRWAYS, BALCONIES AND RAILINGS
Repair
or Replace
The hand/guard rail for the stairs to basement are missing balusters (on both
sides). A fall or injury could occur if not corrected. A qualified contractor
should repair or replace as needed.
3.4
COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS
Repair
or Replace
Sink base is damaged under sink at bottom shelf likely from leaking faucet.
Recommend repair or replace sink base cabinetry as necessary.
3.5
DOORS (REPRESENTATIVE NUMBER)
Repair
or Replace
The Entry door and Closet door rubs at jamb when closing at the Living Room and
hallway closet and Small bedroom. The Living room second door to porch is
painted shut or will not open. A qualified person should repair or replace as
needed.
3.6
WINDOWS (REPRESENTATIVE NUMBER)
Repair
or Replace
There are cracked and broken glass at numerous windows throughout home. At least
five windows missing sash cords at the Living Room, pantry and Small bedroom
(left of hall bath) and at top of stairs. A qualified person should repair or
replace as needed.
4.
Structural Components
4.0
FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or
harmful water penetration into the building or signs of abnormal or
harmful condensation on building components.)
Repair
or Replace
(1) Brick Foundation wall at the basement entry has missing
mortar around windows . Repairs are needed. A skilled masonry
contractor should perform the repairs.
(2) The brick foundation has been coated with a water proof
sealer except behind shelving. If water intrusion occurs here,
then shelving may need removing in order to coat area properly.
4.5
ROOF STRUCTURE AND ATTIC
Repair
or Replace
The common board roofing indicates roof leaks or has leaked around the chimneys.
Leaking roofs should be repaired to prevent damage. I recommend a qualified
contractor perform the work. (See Roof Coverings comments)
5.
Plumbing System
5.0
PLUMBING DRAIN, WASTE AND VENT SYSTEMS
Repair
or Replace
(1) Upon arriving water was on and spilling onto floor of
basement from nearby faucet and water heater. The hvac person
who was their at the time of inspection claimed that he turned
the water on at the street. I turned off the valve at faucet and
water heater. FYI
(2) The stop-valve does not work properly at the Hall Bath sink.
Repairs are needed. The tub drain drains slowly at main bath.
There is a leak under bathtub that can be seen from removing
access panel on wall. Repairs are needed. A qualified licensed
plumber should repair or correct as needed.
(3) The basket strainer is leaking at left side and at right
side at the Kitchen sink. Repairs are needed. A qualified
licensed plumber should repair or correct as needed.
(4) The floor drain has a plug as if to keep something from
coming in? After the inspection, the owner of the adjacent
property volunteered information that the city sewer
occasionally will back up and come into basement. This may be
the reason for the plug? I am unable to determine if plug will
prevent this from occurring. FYI
5.1
PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
Repair
or Replace
(1) The lever on faucet leaks at the kitchen sink. Repairs are
needed to stop leaking water from further damaging the cabinet
bottom or to eliminate moisture that may contribute to fungi
growth. I recommend repair as necessary by a qualified person.
The spray nozzle is not working properly which could be as a
result of no volume or pressure at the kitchen sink. Repairs are
needed. A qualified licensed plumber should repair or correct as
needed.
(2) The water pressure over-all is poor and would not pass
"functional flow." A possible reason for weak volume or pressure
could be old galvanized piping that is corroded inside. NOTE: NO
SHOWER FOR BATH
Toilet will not fill with water likely due to clogged piping. I could not
inspect the toilet fixture for leaks.
5.2
HOT
WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS
Repair
or Replace
Water heater was empty and drain open at bottom when I arrived. I closed drain
but at the end of inspection, drips were still occurring. Repairs may be needed.
6.
Electrical System
6.2
BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF
THEIR AMPERAGE AND VOLTAGE
Repair
or Replace
Problem(s) discovered with Branch Circuits such as doubled wiring at fuse(s),
doubled wiring at circuit(s), and edison base fuse(s) under stairs, and any
other problems that an electrician may discover while performing repairs need
correcting. I recommend a licensed electrician inspect further and correct as
needed.
6.3
CONNECTED DEVICES AND FIXTURES (Observed from a representative
number operation of ceiling fans, lighting fixtures, switches and
receptacles located inside the house, garage, and on the dwelling's
exterior walls)
Repair
or Replace
(1) "Two-prong" outlets are missing cover-plates in the dining
room and in the living room. This is a safety issue that needs
to be corrected. I recommend repair as needed.
(2) Loose light fixture needs securing in closet. Loose or
unfinished wiring in attic should be corrected to remain safe (
Picture 2 ) .One splice box needs a cover-plate in the basement.
I recommend repair as needed ( Picture 4 ) .
7.
Heating / Central Air Conditioning
7.0
HEATING EQUIPMENT
Repair
or Replace
The gas-fired boiler did not function or is non-operational. A repair or
replacement is needed. I recommend further inspection by a licensed HVAC
contractor.
7.3
DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with
supports, insulation, air filters, registers, radiators, fan coil
units and convectors)
Repair
or Replace
Due to the concern for water volume or pressure and because of the old piping
that was turned off for an extended period of time, and the fact that the boiler
is non-operational, I am concerned of whether or not the radiators will function
properly when boiler is repaired. A clogged or failed radiator can be expensive
to replace. I strongly recommend that an HVAC person inspect all the radiators
when boiler becomes operable. You should obtain a letter from the HVAC company
as to the condition of radiators, piping and boiler before you close on home.
7.4
PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM
Repair
or Replace
There is no heat source for Bedroom on right (at top of stairs).
7.5
CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat
systems)
Not
Inspected
The liner for fireplace was partially visible and appears good except for
creosote dust that may conceal a hairline crack until cleaned and inspected by a
licensed chimney sweep. I did not inspect the liner for gas fired boiler. For a
detailed inspection of liner, I recommend a qualified chimney sweep inspect for
safety.
8.
Insulation and Ventilation
8.0
INSULATION IN ATTIC
Inspected
The attic has a small amount of insulation and "Knob and Tube" wiring is
present. As a safety rule Knob and Tube wiring should never have insulation
covering this wire or over heating can occur. If new insulation is added, an
electrician should first replace knob and tubing wires with updated wiring.